C&D Dynasty VR Solar Series Discharge Current Ratings
ModelNo |
1 Hr |
2 Hr |
3 Hr |
8 Hr |
10 Hr |
12 Hr |
16 Hr |
20 Hr |
24 Hr |
36 Hr |
48 Hr |
72 Hr |
100 Hr |
VRS12-33IT |
|
11.8 |
|
|
|
2.64 |
|
1.65 |
|
|
|
0.47 |
0.34 |
VRS12-33HIT |
|
11.8 |
|
|
|
2.64 |
|
1.65 |
|
|
|
0.47 |
0.34 |
VRS12-50IT |
|
17.6 |
|
|
|
3.98 |
|
2.50 |
|
|
|
0.72 |
0.52 |
VRS12-75HIT |
|
26.6 |
|
|
|
6.00 |
|
3.75 |
|
|
|
1.08 |
0.78 |
VRS12-88HIT |
|
29.0 |
|
|
|
6.97 |
|
4.40 |
|
|
|
1.28 |
0.95 |
VRS12-100HIT |
|
31.0 |
|
|
|
7.79 |
|
5.00 |
|
|
|
1.44 |
1.06 |
VRS12-155F |
89.1 |
|
38.1 |
17.1 |
|
12.10 |
|
7.69 |
6.54 |
|
3.41 |
|
1.69 |
VRS12-175F |
103.0 |
|
44.0 |
19.8 |
|
14.00 |
|
8.90 |
7.56 |
|
3.95 |
|
2.00 |
VRS12-215F |
125.0 |
71.5 |
52.7 |
23.5 |
19.30 |
16.42 |
12.69 |
10.40 |
8.79 |
6.00 |
4.56 |
3.11 |
2.28 |